Not found required information?  

  1. Please go to Products in Compact List 

    or
  2. Contact us at contact@redisage.com

C05 C06 C07 C08


Features

  • Serial ports RS232 and RS485
  • Up to 400 simultaneously connected Slave devices
  • ESD Protection for the RS232/485 Data Line
  • 3000 VDC Isolation Protection
  • Power Supply +12 to +30 VDC or 24 VAC
  • Transmission Speed of up to 9600 bps
  • Tx, Rx, Power, and MBus load LED Indicators
  • RS485 Embedded Termination 120 ohm
  • Operating Temperatures, -40 °C to +60 °C
  • DIN-Rail Mounting
  • Dimensions 90x56x35,6 mm
  • 3 Years Warranty
  • Customization or OEM is Welcomed

Introduction

C05-C08 is a family of products that are reliable M-Bus electrical standard converters.
They enable communication in Master mode with many (60-400) simultaneously connected Slave devices and can work as MBus repeaters letting to broaden the range of the interface, while simultaneously making the quality better and supporting the safety of the communication. 
Dedicated EMC integrated circuits guarantee improved connection quality by limiting the impact of interference typical for an industrial environment.

Specifications

Redisage PN

C05

C06

C07

C08

Converter PortsSerial1x RS232, 1x RS485
MBus Masterup to 60 Slavesup to 120 Slavesup to 200 Slavesup to 400 Slaves
MBus Slave1x MBus Slave

Power

Voltage

12-30DC/24AC

Max Power5W8W15W30W
Frame Ground ConnectionYes

Serial
Interface

RS232TxD, RxD, GND
RS485A, B

3000 VDC Isolation Side

RS232, RS485, MBus Slave

Baudrate

up to 9600 bps

LED IndicatorsCommunication Tx, Rx, Power, MBus Load, Error
RS485 Termination120 ohm Manually Enabled
ConnectorRS2323 Pin Terminal Block Max 2,5mm2 Wire
RS4853 Pin Terminal Block Max 2,5mm2 Wire
Power3 Pin Terminal Block Max 2,5mm2 Wire
MBus3 Pin Terminal Block Max 2,5mm2 Wire

Transmission
Distance

RS485

Max. 1,200 m at 9.6 kbps; Max. 400 m at 115.2 kbps
(Belden 9841 2P twisted-pair cable, if different cables are used,
the transmission distance may change)

RS232Max. 15 m at 115.2 kbps
MBusMBus Transmision Distance
Mounting and EnclosureDIN Rail, Plastic PA - UL 94 V0, Black/Green
Temperatures-40°C to +60°C Operating and Storage
Humidity10 - 90% RH, Non-Condensing

ESD Protection

±4kV contact discharge / ±8kV air discharge

Certification CE, RoHS

MBus Max Transmission Distance

Applications

C05-C08 - MBus Converter with MBus repeater functionality

Frame Ground FG

Electronic circuits are constantly prone to electrostatic discharge ESD.
Rediisage Electronics modules feature a design for the frame ground terminal block FG.
The frame ground provides a path for bypassing ESD, which provides enhanced static protection ESD abilities and ensures the module is more reliable.

Connecting FG terminal block to the earth ground will bypass the ESD disturbances outside the device so will provide a better level of protection against ESD.

Frame Ground FG connection referece drawing.

If earth ground is not availabe FG can be left floating or can be connected with power supply GND.

Pin Assignments

C05

C06

C07

C08


Enclosure Dimensions

2U Module Enclosure.
98 x 35.8 x 56.4
Units: mm.

3D Model

Products Family Sample Photo

https://redisage.com

DISCLAMER NOTES

ALL PRODUCT, PRODUCT SPECIFICATIONS, AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.

Datasheet-ID: SC-D